How to use the house electrical load calculator
- Start from the two-bedroom list or clear it, and add your appliances from the list or as "Other".
- Change each appliance's watts to the figure on its rating plate, and enter how many you have and the hours a day it runs.
- Tick "At peak" for everything that runs together at your busiest time, such as a summer evening with the AC on.
- Choose single-phase or three-phase, and read the peak demand, main MCB, wire size, load to apply for and units a month.
Worked example
The starting two-bedroom list has a connected load of 8,834 W. On a summer evening the lights, fans, TV, fridge, computer and a 1.5-ton AC run together: 2,384 W, which at 230 V and a power factor of 0.9 is 11.5 A. With 25% spare that's 14.4 A, so a 16 A main MCB with 2.5 sq mm copper wire or larger, and a sanctioned load of at least 3 kW. A second 1.5-ton AC at peak makes it 3,884 W and 18.8 A; with the spare, 23.5 A needs a 25 A MCB and 4 sq mm wire. Everything on at once would draw 42.7 A, so the geyser, iron, microwave and pump are best run at other times.
The method
- Connected load = Σ watts × number; peak demand = the same for what runs together
- Current = watts ÷ (voltage × power factor); on three-phase, appliances are shared over the phases and the busiest phase counts
- Main MCB = the next standard size (6, 10, 16, 20, 25, 32, 40, 50, 63 A) at or above the peak current plus spare
- Wire: the smallest size whose rating (lower makers' figure) is at least the MCB's
- Sub-circuits (IS 732): lighting at most 10 points and 800 W; power about 3,000 W and two outlets
- Units a month = Σ watts × number × hours a day × 30 ÷ 1,000
An estimate to plan with, not a wiring design: a licensed electrician must size, install and test the wiring to IS 732 and your DISCOM's rules. Everything runs in your browser.